Specifications

Device Configuration
IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 51
Idx Name Byte PC Description
4 R The value required by an upper block's BKCAL_IN so that the
upper block may prevent reset windup and provide bumpless
transfer to closed control loop.
Expressed in PV_SCALE Unit Code.
31 BKCAL_OUT
1 R Back Calculation Status
4 R/W Target setpoint value provided by a supervisory host. Used
when mode is RCAS.
Expressed in PV_SCALE Unit Code.
32 RCAS_IN
1 R/W RCAS_IN Status
4 R/W Target output value provided by a supervisory host. Used
when the mode is ROUT.
Expressed in OUT_SCALE Unit Code.
33 ROUT_IN
1 R/W ROUT_IN Status
34 SHED_OPT 1 R/W Define actions to be taken on remote control device timeout.
4 R Block setpoint Value after ramping - provided by a supervisory
host for back calculations and to allow action to be taken
under limiting conditions or mode change.
Used when mode is RCAS. Expressed in PV_SCALE Unit
Code.
35 RCAS_OUT
1 R RCAS_OUT Status
4 R Block output Value provided to a supervisory host for a back
calculation to allow action to be taken under limiting conditions
or mode change. Used when mode is ROUT.
Expressed in OUT_SCALE Unit Code.
36 ROUT_OUT
1 R ROUT_OUT Status
4 R/W High Range
4 R/W Low Range
2 R/W Unit Index
37 TRK_SCALE
1 R/W Decimal point
All the values are associated with the
external tracking value (TRK_VAL).
38 TRK_IN_D 2 R/W Discrete input used to initiate external tracking of the block
output to the value specified by the TRK_VAL.