Specifications

Device Configuration
IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 47
Idx Name Byte PC Description
72 UPPER_RANGE_
FAILURE
1 R/W Counter for how often the pressure exceeds the upper range
limit.
The counter will be reset by writing any value.
73 LOWER_
SECONDARY_
VALUE_FAILURE
1 R/W Counter for how often the pressure sensor temperature falls
below the lower limit.
The counter will be reset by writing any value.
74 UPPER_
SECONDARY_
VALUE_FAILURE
1 R/W Counter for how often the pressure sensor temperature
exceeds the upper limit.
The counter will be reset by writing any value.
75 LOWER_STATIC_
PRESS_FAILURE
1 R/W Counter for how often the static pressure falls below the lower
sensor limit.
The counter will be reset by writing any value.
76 UPPER_STATIC_
PRESS_FAILURE
1 R/W Counter for how often the static pressure exceeds the upper
sensor limit.
The counter will be reset by writing any value.
77 PTRB_CHANNEL_
MAP
2 R/W This parameter is for the correlation of channels in a device to
channels as defined for a plant or process area.
78 THRESHOLD_
TIME_ADC
1 R/W Time for A/D conversion of the primary value in 10 ms tics. The
TIME_CONST_P_ADC will be deactivated if the primary value
exceeds for longer as the THRESHOLD_TIME_ADC and more
as the THRESHOLD_VAL_ADC the actual output of the
A/D converter.
79 THRESHOLD_
VAL_ADC
4 R/W Threshold value for A/D conversion as percent of the primary
value. The TIME_CONST_P_ADC will be deactivated if the
primary value exceeds for longer as the
THRESHOLD_TIME_ADC and more as the
THRESHOLD_VAL_ADC the actual output of the
A/D converter.
80 TIME_CONST_
P_ADC
4 R/W Time constant for the static pressure A/D conversion lower or
equal then 1.
The time constant is zero with value of 1.
81 TIME_CONST_
T_ADC
4 R/W Time constant for sensor temperature A/D conversion lower or
equal then 1.
The time constant is zero with value of 1.
82 MEAS_
INTEGRATION_
TIME_ADC
1 R/W Integration time for primary value (pressure) A/D conversion in
100 ms tics.
Range 0 … 13.
83 SECONDARY_
VALUE_1
4 R Only for internal use.
84 PERCENT_RANGE 4 R Only for internal use.