Specifications
Device Configuration
46 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01
Idx Name Byte PC Description
58 TAB_OP_CODE 1 58 Modification type for linearization curve.
59 TAB_STATUS 1 59 Status for values of linearization curve.
60 TAB_ACTUAL_NUM
BER
1 60 Actual number of X / Y values for linearization curve.
61 TAB_X_Y_VALUE_A 4 X / Y values from number 1 to 11.
62 TAB_X_Y_VALUE_B 4 X / Y values from number 12 to 12.
63 MAX_SENSOR_
VALUE
4 R/W Drag indicator for maximum pressure value.
The drag indicator will be reset by writing any value.
64 MIN_SENSOR_
VALUE
4 R/W Drag indicator for minimum pressure value.
The drag indicator will be reset by writing any value.
65 MAX_SECONDARY
_VALUE
4 R/W Drag indicator for maximum pressure sensor temperature.
The drag indicator will be reset by writing any value.
66 MIN_SECONDARY_
VALUE
4 R/W Drag indicator for minimum pressure sensor temperature.
The drag indicator will be reset by writing any value.
67 MAX_STATIC_
PRESSURE
4 R/W Drag indicator for maximum static pressure value.
The drag indicator will be reset by writing any value.
68 MIN_STATIC_
PRESSURE
4 R/W Drag indicator for minimum static pressure value.
The drag indicator will be reset by writing any value.
69 LOWER_SENSOR_
FAILURE
1 R/W Counter for how often the pressure falls below the lower
sensor limit.
The counter will be reset by writing any value.
70 UPPER_SENSOR_
FAILURE
1 R/W Counter for how often the pressure exceeds the upper sensor
limit.
The counter will be reset by writing any value.
71 LOWER_RANGE_
FAILURE
1 R/W Counter for how often the pressure falls below the lower range
limit.
The counter will be reset by writing any value.