Specifications
Device Configuration
IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 45
Idx Name Byte PC Description
Linearization type:
51 LIN_TYPE 1 R/W
2 Linear
3 Square root
4 Square root to the third
power
5 Square root to the fifth
power
240 Linearization curve
241 Spherical tank
242 Cylindric lying tank
4 R/W High Range
4 R/W Low Range
2 R/W Unit Index
52 SCALE_IN_RANGE
1 R/W Decimal point
All the values represent the input scaling.
See also 8.4. Only Pressure unit code is
usable. See in the Analog Input Function
Block Table the XD_SCALE Unit Code the
allowed Code for Pressure.
53 SET_UPPER_
RANGE
1 R/W The upper range value will be set with writing of the value 2.
54 SET_LOWER_
RANGE
1 R/W The lower range value will be set with writing of the value 2.
4 R/W High Range
4 R/W Low Range
2 R/W Unit Index
55 STATIC_
PRESSURE_
RANGE
1 R/W Decimal point
All the values represent the input scaling.
See also 8.4. Only Pressure unit code are
usable See in the Analog Input Function
Block Table the XD_SCALE Unit Code the
allowed Code for Pressure.
56 LOW_FLOW_CUT_
OFF
4 R/W Limit used in square root processing. A value of zero percent
of scale is used in block processing if the transducer falls
below this limit, in % of input scale. The features may be used
to eliminate noise near zero for a flow sensor.
57 FLOW_LIN_SQRT_
POINT
R/W Limit used in square root processing. Starting from the
LOW_FLOW_CUT_OFF value a linear part is applied before to
apply the square root function.
The FLOW_LIN_SQRT_POINT is effect less if the value is set
lower then the LOW_FLOW_CUT_OFF.