Specifications
Device Configuration
44 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01
Idx Name Byte PC Description
Number of remote seals:
40 NUMBER_
REMOTE_SEAL
1 R/W
1 One Seal
2 Two Seals
251 None
Fill fluid of remote seal:
41 REMOTE_SEAL_
FILL_FLUID
2 R/W
1 Silicon oil
2 Fluorcarbon
3 Distilled water
4 High temperature oil
5 Vegetable oil
6 Mineral oil
7 White oil
8 Fill fluid FDA certified
Type of materials for RS isolator:
42 REMOTE_SEAL_
ISOLATOR_
MATERIAL
2 R/W
3 Hastelloy C
4 Monel
5 Tantalum
19 AISI 316L, Stainless Steel
43 SECONDARY_
VALUE_TRIM_
VALUE
4 R/W Trim value for pressure sensor temperature.
44 SECONDARY_
VALUE_HI_LIM
4 R Maximum limit for trim value for pressure sensor temperature.
45 SECONDARY_
VALUE_LO_LIM
4 R Minimum limit for trim value for pressure sensor temperature.
46 STATIC_PRESS_
PRIMARY_VALUE_
TYPE
2 R/W The primary value type for static pressure is always 109:
Absolute Pressure
4 R Value of static pressure measurement. 47 STATIC_
PRESSURE_VAL
1 R Status of static pressure measurement.
48 STATIC_
PRESSURE_CAL_
POINT_HI
4 R/W Upper calibration point for static pressure.
49 STATIC_
PRESSURE_CAL_
POINT_LO
4 R/W Lower calibration point for static pressure.
50 STATIC_
PRESSURE_CAL_
MIN_SPAN
4 R Minimal span for static pressure calibration.