Specifications

Device Configuration
42 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01
Idx Name Byte PC Description
26 SENS_CAL_WHO 32 R/W The name of the person responsible of the last sensor
calibration.
Type of materials for sensor isolator:
27 SENS_ISOL_MTL 2 R
3 Hastelloy C
4 Monel
5 Tantalum
19 AISI 316L Stainless
Steel
136 Monel Gold Plated
Type of Fill Fluid used in the sensor:
28 SENSOR_FILL_
FLUID
2 R
1 Silicone Oil
2 Fluorcarbon
3 Fluorcarbon
7 With Oil (FDA)
4 R This is the Sensor temperature value to be linked in input to
the AIFB when the CHANNEL = 2 is selected. It is expressed
in SECONDARY_VALUE_UNIT_1
29 SECONDARY_
VALUE_1
1 R This is the Sensor temperature Status.
Sensor Temperature Unit. The allowed units are: 30 SECONDARY_
VALUE_UNIT_1
2 R/W
1000 Kelvin
1001 Celsius Degree
1002 Fahrenheit Degree
1003 Rankine Degree
31 ZERO_POINT_
CORRECTION
1 R/W The sensor oblique will be corrected with writing of the value 2.
The process connection must be pressure free.
32 MODUL_TYPE 2 R Type of pressure sensor.
33 STATIC_
PRESSURE_
SENSOR_RANGE
4 R Static pressure sensor range for differential pressure sensor.
Rated pressure, max. operating pressure. 34 RATED_PRESSURE 1 R
2 PN6
6 PN100
7 PN250
12 PN160
15 PN41
Type of materials for the O-ring:
35 PROCESS_
CONNECTION_
O_RING_MTL
2 R/W
12 Buna
11 Viton
133 Perfluoro elastomer
138 EPDM
251 None