Specifications
Device Configuration
IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 41
Idx Name Byte PC Description
4 R This is the output value from the TB and input for the AIFB
when CHANNEL = 1. It is always represented in the
PRIMARY_VALUE_RANGE Unit-Index.
14 PRIMARY_VALUE
1 R This is the output status from the TB.
4 R High Range
4 R Low Range
2 R Unit Index
15 PRIMARY_VALUE_
RANGE
1 R Decimal point
All the values are associated with the
PRIMARY_VALUE.This record is read only
and it is always a copy of the XD_SCALE of
the AIFB having the Channel = 1.
Whenever writing on XD_SCALE of the
AIFB with CHANNEL = 1 are performed,
the PRIMARY_VALUE_RANGE is updated
in the same way. The usable units“ code is
the same of the XD_SCALE in the Analog
Input Function Block.
16 CAL_POINT-_HI 4 R/W The Highest calibrated value
17 CAL_POINT-_LO 4 R/W The lowest calibrated value
18 CAL_MIN_SPAN 4 R The minimum span to be used between the calibrations points,
high and low.
19 CAL_UNIT 2 R/W Calibration Unit. Only Pressure Units are allowed. See in the
Analog Input Function
Block Table the XD_SCALE Unit Code the allowed
Code for Pressure.
20 SENSOR_TYPE 2 R/W Type of sensor.
The 2600T is -121 - Pressure sensor unknown.
4 R High Range
4 R Low Range
2 R Unit Index
21 SENSOR_RANGE
1 R Decimal point
All the values represent the physical sensor
limits. See in the Analog Input Function
Block Table the XD_SCALE Unit Code the
allowed Code for Pressure.
22 SENSOR_SN 32 R Serial Number of the sensor
23 SENSOR_CAL_
METHOD
1 R/W Calibration Method
24 SENS_CAL_LOC 32 R/W The last location of the sensor Calibration.
25 SENS_CAL_DATE 7 R/W The last date on which the calibration was performed.