Specifications

Device Configuration
40 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01
Idx Name Byte PC Description
The block alarm is used for all configuration, hardware, and
connection failure or system problems in the block. The cause
of the alert is entered in the sub-code field. The first alert to
become active will set the Active Status in the status
parameter. As soon as the Unreported status is cleared by the
alert reporting task, another block alert may be reported
without clearing the Active Status, if the sub-code has
changed.
1 R/W Unacknowledged
1 R Alarm State
8 R Time Stamp:
The date and time of when the alert was generated.
2 R Sub-code
8 BLOCK_ALM
1 R Value
9 TRANSDUCER_
DIRECTORY
4 R Directory that specifies the number and starting indices of the
transducers in the transducer block.
10 TRANSDUCER_
TYPE
2 R Identifies the transducer type.
For the 2600T FF it is 100 = Standard Pressure with
calibration.
11 XD_ERROR 1 R Transducer block error sub-code
12 COLLECTION_
DIRECTORY
36 R Directory that specifies the number, starting indices, and the
DD items IDs of the data collections in each transducer within
a transducer block.
Type of measurement representing the primary value.
The default measurement type is Differential Pressure.
13 PRIMARY_VALUE_
TYPE
2 R
100 Mass Flow
101 Volumetric Flow
107 Differential Pressure
108 Gauge Pressure
109 Absolute Pressure
110 Level
200 Volume