Specifications

Device Configuration
IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 39
10.4 Pressure Transducer Block
The modification of the flow configuration with 267C / 269C transmitters is only possible with the
“Device Management Application” (DMA). In this reason, have parameters with influence to the
flow calculation with 267C / 269C transmitters different from this table a read only attribute.
Idx Name Byte PC Description
0 BLOCK_OBJ 62 mix. In the Block Object data structure, there are different items
describing the block characteristics. Execution period, Number
of parameters in the block, the DD Revision, Profile Revision,
View Objects characteristics and so on.
1 ST_REV 2 R The revision level of the Static data associated with the
Function Block. The revision level is incremented each time a
static parameter value in the block is changed.
2 TAG_DESC 32 R/W The user description of the intended application of the block.
3 STRATEGY 2 R/W The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
4 ALERT_KEY 1 R/W The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
1 R/W Target - The selected mode from the operator.
1 R Actual - The mode the block is currently in.
1 R/W Permitted - Allowed modes that the target may take on.
5 MODE_BLK
1 R/W Normal - The common mode for the Actual.
6 BLOCK_ERR 2 R This parameter reflects the error status associated with the
hardware or software components associated with a block. It is
a bit string, so that multiple errors may be shown.
This alert is generated by any change to the static data.
1 R/W Unacknowledged
1 R Update State
8 R Time Stamp:
The date and time of when the alert was generated.
2 R Static Revision
7 UPDATE_EVT
2 R Relative Index