Specifications

Device Configuration
IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 37
Idx Name Byte PC Description
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active will set the Active Status in the status
parameter. As soon as the Unreported status is cleared by the
alert reporting task, another block alert may be reported
without clearing the Active Status, if the subcode has changed:
2 R Current
2 R Unacknowledged
2 R Unreported
22 ALARM_SUM
2 R/W Disabled
23 ACK_OPTION 2 Used to set auto acknowledgment of the alarms.
24 ALARM_HYS 4 Amount the PV must return within the alarm limit before the
alarm condition clears. Alarm Hysteresis is expressed as
percent of the OUT_SCALE span.
25 HI_HI_PRI 1 R/W Priority of the High High Alarm
26 HI_HI_LIM 4 R/W The setting of the High High Limit producing the High High
Alarm.
This value is expressed in OUT_SCALE Unit Code
27 HI_PRI 1 R/W Priority of the High Alarm
28 HI_LIM 4 R/W The setting of the High Limit producing the High Alarm.
This value is expressed in OUT_SCALE Unit Code
29 LO_PRI 1 R/W Priority of the Low Alarm
30 LO_LIM 4 R/W The setting of the Low Limit producing the Low Alarm.
This value is expressed in OUT_SCALE Unit Code.
31 LO_LO_PRI 1 R/W Priority of the Low Low Alarm
32 LO_LO_LIM 4 R/W The setting of the Low Low Limit producing the Low Low
Alarm.
This value is expressed in OUT_SCALE Unit Code: