Specifications

Device Configuration
36 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01
Idx Name Byte PC Description
17 LOW_CUT 4 R/W Limit used in square root processing. A value of zero percent
of scale is used in block processing if the transducer falls
below this limit, in % of scale.
The features may be used to eliminate noise near zero for a
flow sensor.
18 PV_FTIME 4 R/W Time constant of a single exponential filter for the PV,
expressed in seconds.
This is the time necessary for reach the 63 % of the variation in
input
4 R The percent of the value from the Transducer block or from the
simulation value, when enabled, before the characterisation
(L_TYPE) and Filtering (PV_FTIME).
19 FIELD_VAL
1 R Field Value Status
This alert is generated by any change to the static data.
1 R/W Unacknowledged
1 R Update State
8 R Time Stamp:
The date and time of when the alert was generated.
2 R Static Revision
20 UPDATE_EVT
2 R Relative Index
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active will set the Active Status in the status
parameter. As soon as the Unreported status is cleared by the
alert reporting task, another block alert may be reported
without clearing the Active Status, if the subcode has changed.
1 R/W Unacknowledged
1 R Alarm State
8 R Time Stamp:
The date and time of when the alert was generated.
2 R Subcode
21 BLOCK_ALM
1 R Value