Specifications
Device Configuration
32 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01
10.3 Analog Input Function Block
Idx Name Byte PC Description
0 BLOCK_OBJ 62 mix. In the Block Object data structure, there are different items
describing the block characteristics. Execution period, Number
of parameters in the block, the DD Revision, Profile Revision,
View Objects characteristics and so on.
1 ST_REV 2 R The revision level of the Static data associated with the
Function Block. The revision level is incremented each time a
static parameter value in the block is changed.
2 TAG_DESC 32 R/W The user description of the intended application of the block.
3 STRATEGY 2 R/W The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
4 ALERT_KEY 1 R/W The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
1 R/W Target - The selected mode from the operator.
1 R Actual - The mode the block is currently in.
1 R/W Permitted - Allowed modes that the target may take on.
5 MODE_BLK
1 R/W Normal - The common mode for the Actual.
6 BLOCK_ERR 2 R This parameter reflects the error status associated with the
hardware or software components associated with a block. It is
a bit string, so that multiple errors may be shown.
4 R The process variable used in block execution, expressed in
XD_SCALE unit Code.
7 PV
1 R The process variable status
4 R The block output value calculated as a result of the block
execution, expressed in OUT_SCALE unit code
Only when the function block is in Manual MODE this
variable can be written
8 OUT
1 R The block output status
1 R/W Simulate Transducer Status
4 R/W Simulate Transducer Value
1 R Simulate Transducer Status
4 R Simulate Transducer Value
9 SIMULATE
1 R/W Simulation Enable/Disable bit