062 Behaviour of exist mode internal active
(B)
To change the property of the exit mode for internal active
(B):
1. On the control unit, enter:
062
2. The LCD display shows: 062: B=LEISE
3. Via the keypad, select from the following items
and press:
0
Low Tone
The acoustic signal during the exit
delay time is emitted at half volume.
1
Instant
During internal activation, the alarm
centre is internally activated
immediately – i.e., without delay.
2
Silent
No acoustic signal is emitted during the
delay time. Following expiry of the delay
time, the alarm centre emits a brief
signal.
3
B=A
The initial mode for internal active B is
as for the initial mode of overall active A
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
063 Alarm behaviour for internal active (B)
To change the alarm property for internal active (B):
1. On the control unit, enter:
063
2. The LCD display shows: 063: B=Keypad
3. Via the keypad, select from the following items
and press:
0
B=Keypad
Only the control units are activated.
1
B=Internal
On alarm, the control units and the
internal alarm are activated.
2
B=Local
On alarm, the control units, the internal
alarm and the external siren are
activated.
3
B=Full
On alarm, the control units, the internal
signalling, the external sirens and the
telephone dialler are activated.
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double “beep” tone and shows Installer Mode.
065 Exit delay time internal B
To change the property of the exit delay time for internal
active B:
1. On the control unit, enter:
065
2. The LCD display shows: 065: Exit B=20
3. Via the keypad, select from the following items
and press:
1
Exit B=10
Exit delay time for internal active B is 10
seconds.
2
Exit B=20
Exit delay time for internal active B is 20
seconds.
3
Exit B=30
Exit delay time for internal active B is 30
seconds.
4
Exit B=45
Exit delay time for internal active B is 45
seconds.
5
Exit B=60
Exit delay time for internal active B is 60
seconds.
6
Exit B=120
Exit delay time for internal active B is
120 seconds.
4. Confirm your input. On the control unit, enter:
.