16. Technical data
TTR 200
Parameter Value*
Article number 1.110.000.010
EAN 4.052.0138.007.464
Dehumidification performance approx. 0.3 kg/h
Air volume 40 to 120 m³/h
Nominal air volume/pressing approx. 80 m³/h / 50 Pa
Regeneration air volume approx. 15 m³/h
Intake temperature -15 °C to +35 °C
Ambient temperature -20 °C to +40 °C
Power connection 230 V, 50/60 Hz
Power consumption (overall) 0.43 kW
Power consumption (heating) 0.39 kW
min. / opt. / max. heating flow 1.0 / 1.6 / 2.2 A
Width 260 mm
Height 286 mm
Depth 306 mm
Weight 9.5 kg
* at 20°C/60% rh
TTR 300
Parameter Value*
Article number 1.110.000.015
EAN 4.052.0138.007.471
Dehumidification performance approx. 0.65 kg/h
Air volume 80 to 250 m³/h
Nominal air volume/pressing approx. 200 m³/h / 100 Pa
Parameter Value*
Regeneration air volume approx. 30 m³/h
Intake temperature -15 °C to +35 °C
Ambient temperature -20 °C to +40 °C
Power connection 230 V, 50/60 Hz
Power consumption (overall) 0.87 kW
Power consumption (heating) 0.80 kW
min. / opt. / max. heating flow 2.2 / 2.8 / 3.4 A
Width 310 mm
Height 350 mm
Depth 340 mm
Weight 12 kg