User guide

0
20
40
60
80
100
0 102030405060708090100
Percent Input
Percent Output
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
0 100 200 300 400 500 600
Input Signal (mV)
Output Signal (mA)
Break Points
Actual Non-linear
Relationship
I-E67-84-1B February,2002 8-20
6) Set the output percentage for the first
break point (Y-1) using the Key to
increment the blinking digit and the
Key to move to the next digit, and press
the ENTER Key to enter the new value.
7) Repeat steps 5 and 6 for the remaining
four break points.
Table 8-5. Non-linear Output Example Values
Break ORP Signal Output Range Percent Input Percent Output
Point (mV) (mA) (%) (%)
0 4.0 0 0
1 120 5.6 20 10
2 270 8.8 45 30
3 360 12.0 60 50
4 420 15.2 70 70
5 540 19.2 90 95
600 20.0 100 100
Figure 8-6. Non-linear Output Break Point Determination.
Table 8-5 and Figure 8-6 illustrate the use of
the Non-linear Output function. This
information is only for illustration purposes