User guide

I-E67-84-1B February,2002 8-16
State using the NEXT Key.
3) Set the TC.TYPE to AUT.SOL using the
ENTER Key.
4) Set the PH/10C or MV/10C value (as the
case may be) using the Key to
increment the blinking digit and the
Key to move to the next digit and
pressing the ENTER Key to enter the new
value.
Analog Output One State (Basic/Advanced)
The Analog Output One State sets the output
span, range, and function. The output span is
software selectable for either zero to 20
milliamperes or four to 20 milliamperes and is
source to the Primary Process Variable. For
Basic configurations, the output function can
only be linear. Lower and upper range values
must be entered and are defaulted to the full
scale process variable range (e.g., 0-14 pH
for pH Analyzer States). For Advanced
configurations, the output function can be
linear or non-linear. For a non-linear
output, lower and upper range values must also
be entered as well as five break points.
Linear Output State (Basic/Advanced)
The Linear Output State establishes the lower
and upper range values. The default values
for the output represent the full scale
process variable range (e.g., 0-14 pH).
For a reverse acting output, reverse the zero
or four and 20 milliampere values (e.g., 14 pH
for the zero or four milliampere value and 0
pH for the 20 milliampere value).