Tripping characteristics
Tripping characteristics
Acc. to Tripping
characte-
ristics
Rated
current
Thermal release
1)
Electromagnetic release
2)
I
n
Currents:
conventional
non-tripping
current
I
1
conventional
tripping
current
I
2
Tripping
time
Range of
instantaneous
tripping
Tripping time
IEC/EN 60947-2 C 0.5 to 63 A 1.05 · I
n
1.3 · I
n
> 1 h
< 1 h
3)
5 · I
n
10 · I
n
> 0.2 s
< 0.2 s
K 0.2 to 63 A 1.05 · I
n
1.3 · I
n
> 1 h
< 1 h
3)
10 · I
n
14 · I
n
> 0.2 s
< 0.2 s
Z 0.5 to 63 A 1.05 · I
n
1.3 · I
n
> 1 h
< 1 h
3)
2 · I
n
3 · I
n
> 0.2 s
< 0.2 s
1)
The thermal releases are calibrated to a nominal reference ambient temperature of 30 °C.
In the case of higher ambient temperatures, the current values fall by approx. 6 % for each 10 K temperature rise.
2)
The indicated tripping values of electromagnetic tripping devices apply to a frequency of 50/60 Hz. The thermal release operates independent of frequency.
3)
As from operating temperature (after I
1
> 1h)
C characteristic