2. To modify an existing topic, select the topic name and click on Modify. To define a
new topic, click on New. The "Topic Definition" dialogue box will appear:
3. Enter the Topic Name.
Note: If using InTouch the same Topic Name is to be entered in the "Add Access Name"
dialogue box described in the Using the SPA Server with InTouch section.
4. Click on the ComPort button to associate a communication port with the topic.
Note: Additional topics may be associated with the same communication port later.
5. Select the corresponding SPA Device. These devices (units) should be defined in the
Unit Definition File. For details see the SPA Server Unit Definition File section.
Note: There must be at least one SPA unit defined in the SPA Server Unit Definition File,
otherwise the SPA Server will not work.
6. Enter a unique, same as set on connected SPA device, Station Number. The range
of Station Number is 0…999, except 900.
7. Set the Update Interval field to indicate the frequency (in milliseconds) the items on
this topic will be read (polled). The default value is 1000 milliseconds.
8. Check or uncheck the Poll Events checkbox. If Poll Events checkbox is checked
then events of this Station are requested (polled) at event Update Interval. If this
checkbox is not checked then no event polling is performed.
9. Set the event Update Interval field to indicate the frequency (in milliseconds) the
events will be polled from this Station.