4.7 ID-Signals Sheet
ID-Signals are only used by the Procontrol P13 Connect OPC server for command output. ID-Signals are not loaded to
S+ Operations. The fields are described in the following table.
Table 4-6: S+ P13 Engineering Workbook- Fields for ID-Signals
OPC Field
Meaning
Value
Type
Tag type
DO
Name
Tag name
String
Descr
Tag description
String
Bus
Bus number
Station
Station number
Hex, 00,..,3F
Device
Device Number
Hex, 00,..,FF
Bit
Bit Number
Section
Section
Text1
Text for 1-state
Text
Text0
Text for 0-state
Text
Priority
Priority for alarm
EventDef
Event definition:
0: No message
1: Message if Normal->Active
2: Message if Active->Normal
3: Message both directions
NormPos
Which is normal (not active) state
{0,1}
Inverted
Field value to be inverted
{Y, N}
Output
Output the value
{Y, N}
4.8 Special Objects Sheet
The following special objects are configured in this sheet:
Table 4-7: S+ P13 Engineering Workbook –Special Objects Sheet
Special Object Type
Object Name
Meaning
required
P13CON
P13 Connectivity
Serves in S+ Operations as target
object for P13 system messages.
yes
Bus
Bus <Bus Number>
e.g. : Bus 5
37
Provides data items for bus status.
optional
Station
<BusAddr>-
STN<StationAddr>
e.g. : 5-STN3E
38
Provides data items for station status.
39
optional
The fields are described in the following table.
Table 4-8: S+ P13 Engineering Workbook- Fields for Special Objects
Field
Object Type
P13CON
BUS
STATION
NAME
e.g.
P13 Connectivity
e.g.
BUS 5
e.g.
5-STN3E
DESC
Procontrol P13 Connectivity
Server
Bus 5
Station 3E on Bus 5
37
Name must follow this pattern.
38
Name must follow this pattern.
39
Station monitoring must be available in the Plant and configured correctly in the OPC server.