Product specifications

SPlus Operations P13 Connectivity Guide S+ P13 ENGINEERING WORK BOOK
2VAA001153C 73
EventDef
-
x
-
Event definition:
0: No message
1: Message if Normal->Active
2: Message if Active->Normal
3: Message both directions

NormPos
-
x
-
Which is normal (not active)
state
{0,1}
Inverted
-
x
-
Field value to be inverted
{Y, N}
RangeLow
LINS_LIMT
-
x
Measuring range low
Float
RangeHigh
HINS_LIMT
-
x
Measuring range high
Float
Unit
EUDESC
-
x
Measuring unit
Text
NoDecs
NUMDECPL
-
x
No of decimal places

DRLow
SCA_VAL_0
-
x
Display range low
Float
DRHigh
SCA_VL_100
-
x
Display range high
Float
LimValue1Lim
Value2
LimValue3Lim
Value4
L2ALARM
L1ALARM
H1ALARM
H2ALARM
x
Limit <n> value
Float
LimType1
(...2,3,4)
-
x
Limit <n> type
0: Upper
1: Lower
LimTreat1
(...2,3,4)
-
x
Limit <n> treatment
(see EventDef field)

LimPrio1
LimPrio2
LimPrio3
LimPrio4
ALPRI_2L
ALPRI_1L
ALPRI_1H
ALPRI_2H
x
Limit <n> priority
0,4: Status
1,2,3: Alarm

2,3,4)
-
x
Limit <n> alarm text
Text
SpecProc
-
(x)
(x)
Special processing identifier
36
Text
Output
-
DOX
AOX
Output the value
{Y, N}
-
FIELD_AD1
x
x
Refresh Time
500
-
FIELD_AD2
x
x
Read type
120
(By exception)
-
TAGTYPE
x
x
S+ Operations tag type
{Analog, Digital}
-
TAGSRC
x
x
Data source for S+ Opeations
PROP13
-
OPCEXPCLNT
x
x
Allow output (commands) to
OPC server
Y
-
ALMGROUP
x
x
Alarm group

-
ALMREM
x
x
Remote alarm processing
Y
-
FIELD_TX1
x
x
OPC DA server
ABBProcontrolP13.
OPC.1
-
FIELD_TX3
x
x
OPC DA item name
= Name
-
FIELD_TX5
x
x
OPC AE server
ABBProcontrolP13.
Event.1
-
FIELD_TX7
x
x
OPC AE source item name
= Name
-
DATA_PROC
x
x
S+ Operations Data Processor
PROP13.Block.P13.
<type> e.g.
PROP13.Block.P13.
AIX
FACEPLATE
x
x
Faceplate
Prctrl.POP_P13<typ
e>
e.g.
Prctrl.POP_P13AIX
36
See Table 4-3:Available Special Processing for Signals