Product specifications

SPlus Operations P13 Connectivity Guide S+ P13 ENGINEERING WORK BOOK
72 2VAA001153C
4.3 Column Headings Field Names
Both, the S+ Operations tag import and the S+ P13 OPC Builder work with column headings to identify the columns and
not with the column positions. The columns used and the field designations are different for the two utilities. Therefore
two rows with column headings are provided.
Figure 4-2: Column Headings in the S+ P13 Workbook
4.4 Named Ranges in S+ P13 Engineering Workbook
Within the worksheets some named ranges have to be defined
Table 4-1: Named ranges in the S+ P13 Engineering Workbook
Worksheet
Named Range for S+ Opeations
Named Range for S+_P13 OPC Builder
Signals
Database
P13OPC_Signals
Control Objects
Database
P13OPC_ControlObjects
Special Objects
Database
Not used
ID-Signals
Not Used
P13OPC_IDSignals
The named ranges must include all columns used by the corresponding target (S+ Operations tag import or S+ P13
OPC Builder). The named ranges for the S+ Operations tag import must not include the heading row for the S+ P13
OPC Builder. The named ranges for the S+ P13 OPC Builder will contain the heading row for the S+ Operations tag
import. This row will be ignored by the S+ P13 OPC Builder.
4.5 Signals Sheet
The Signals sheet contains analog and binary inputs and outputs. The fields are described in the following table.
Table 4-2: S+ P13 Engineering Workbook Fields for Signals
OPC Field
S+ Operations
Field
DIX/DOX
AIX/AOX
Meaning
Value
Type
-
x
x
Tag type
{DIX,DOX,AIX,AOX}
Name
NAME
x
x
Tag name
Text
Descr
DESC
x
x
Tag description
Text
Bus
OUT1_TX1
x
x
Bus number

Station
OUT1_TX2
x
x
Station number
Hex, 00,..,3F
Device
OUT1_TX3
x
x
Device Number
Hex, 00,..,FF
Bit
OUT1_TX4
x
-
Bit Number
Hex
Section
PLANTUNIT
x
x
Section

Text1
ONESTATE
x
-
Text for 1-state
Text
Text0
ZEROSTATE
x
-
Text for 0-state
Text
Priority
AL_PRI
x
-
Priority for alarm

Field designation for SPlus P13 Builder
Field designation for SPlus Operations Tags Import