Product specifications
SPlus Operations P13 Connectivity Guide PROCONTROL P13 OPC SERVER
68 2VAA001153C
For the global acknowledge signal :
VPCDEF1,ACKN
If the global signals are the same for all busses, the configuration must look as follows:
Global signals valid for all busses :
VPCDEF1,REL,<RelSig AllBusses>,*
VPCDEF1,ACKN,<AcknSig AllBusses>,*
3.9.2.3 Identifying Individual Command Signals
The individual command signals are identified by a corresponding naming convention:
<Control Object Name>_<Command Signal Code>
The command signal codes are dependant from the control object type. They can be defined by corresponding
parameter set records in the pve-file as shown in the following list:
VPCDEF1,ASE,<ACKN>,<ON>,<OFF>
(AS160OS: DCTS)
VPCDEF1,ASS,<ACKN>,<OPEN>,<CLOSE>,<HOLD>
(AS160OS: DCS)
VPCDEF1,ASM,<ACKN>,<ON>,<OFF>
(AS160OS: DCSV)
VPCDEF1,SWV,<ACKN>,<RAISE>,<LOWER>
(AS160OS: SPI)
VPCDEF1,GSA,<ACKN>,<ON>,<OFF>,<HOLD>
(AS160OS: GRC)
VPCDEF1,VW2,<ACKN>,<SEL1>,<SEL2>
(AS160OS: SEL2)
VPCDEF1,VW3,<ACKN>,<SEL1>,<SEL2>,<SEL3>
(AS160OS: SEL3)
VPCDEF1,VW4,<ACKN>,<SEL1>,<SEL2>,<SEL3>,<SEL4>
(AS160OS: SEL4)
3.9.2.4 Special Parameters
With the VPCDEF1, DELAY1 instruction, the additional length in milliseconds of the global acknowledge signal
can be defined. Default value is 50 ms.
Example:
VPCDEF1, DELAY1, 60
With the MSGFILTER instruction, warnings in the message log can be suppressed. This can be useful, to
suppress warnings for regularly missing commands after commissioning.
Example:
MSGFILTER, 1
This instruction suppresses warnings.
3.10 VPC Mode “Mixed Mode I”
3.10.1 Concept
is a mix of two VPC concepts. In this mode, analog control objects as ASP, HST etc. are
egram and ID-Sig. This means that these control objects use the XC13 telegram and one
or two ID-Signals
35
concept (see 3.9 ).
3.10.2 Engineering
3.10.2.1
This selection has to be done via PServer User Interface General->VPC Modes.
35
In submode RMPI, ramping SWVs use (see 3.10.2.4 )