Product specifications

SPlus Operations P13 Connectivity Guide PROCONTROL P13 OPC SERVER
62 2VAA001153C
Name
Meaning
Data Type
Engin.
Para.
OPC Prop.
OPC Item
Operable
Object is operable
Bool
x
Operable
Station
Station number
String
Station
Type
PV Type
String
x
Type
SubType
Subtype
String
x
SubType
Error
Set if signal error in one
of the feedbacks
Short
Error
XC80Tel
See
3.4.5 Support for XC80-
Telegram
UI2
XC80Tel
XC80Def
UI2
XC80Def
XC80Dist
UI2
XC80Dist
XC80Bus
I2
(x)
XC80Bus
XC80Station
String
(x)
XC80Station
XC80Device
String
(x)
XC80Device
3.7.4.3.2 Binary Control (ASE, ASS, ASM)
Table 3-38: Specific Attributes for Binary Control Objects
Name
Meaning
Data Type
Engin.
Para.
OPC Prop.
OPC Item
ASE
ASM
ASS
GSA
ACKN
Acknowledge
Command
Bool
CMD_ACKN
x
x
x
AUTOMAN
Auto/Manual
Command
Bool
CMD_AUTO
MAN
ON
On/Open
Command
Bool
CMD_ON
30
x
x
OFF
Off/Close
Command
Bool
CMD_OFF
31
x
x
STOP
32
Stop Command
Bool
CMD_STOP
DMS
DMS Command
Bool
CMD_DMS
x
x
x
PROTOFF
Signal reference
for Protection
OFF
String
PROTOFF
x
x
x
PROTON
Signal reference
for Protection
ON
String
PROTON
x
x
x
RELOFF
Signal reference
for Release OFF
String
RELOFF
x
x
x
RELON
Signal reference
for Release ON
String
RELON
x
x
x
XL18
XL18 signal PV
DI
(see DIX)
x
x
x
XL19
XL19 signal PV
DI
(see DIX)
x
x
x
XL28
XL28 signal PV
DI
(see DIX)
x
x
x
XL29
XL29 signal PV
DI
(see DIX)
x
x
x
XL68
XL68 signal PV
DI
(see DIX)
x
x
x
XL69
XL69 signal PV
DI
(see DIX)
x
x
x
30
CMD_OPEN for ASS
31
CMD_CLOSE for ASS
32