Product specifications

SPlus Operations P13 Connectivity Guide PROCONTROL P13 OPC SERVER
2VAA001153C 61
Name
Meaning
Data Type
Engin.
Para.
OPC Prop.
OPC Item
ACKN
Acknowledge Command
Bool
CMD_ACKN
AUTOMAN
Auto/Manual Command
Bool
CMD_AUTOM
AN
ON
On/Open Command
Bool
CMD_ON
25
OFF
Off/Close Command
Bool
CMD_OFF
26
STOP
27
Stop Command
Bool
CMD_STOP
DMS
DMS Command
Bool
CMD_DMS
3.7.4.2.3 Selector Control (SCO)
Table 3-35: Specific Attributes for Selector Control Objects
Name
Meaning
Data Type
Engin.
Para.
OPC Prop.
OPC Item
ACKN
Acknowledge Command
Bool
CMD_ACKN
SEL1
Select 1
Bool
CMD_SEL1
SEL2
Select 2
Bool
CMD_SEL2
SEL3
1
Select 3
Bool
CMD_SEL3
SEL4
1
Select 4
Bool
CMD_SEL4
DMS
DMS command
Bool
CMD_DMS
3.7.4.2.4 Analog Control (ACO)
Table 3-36: Specific Attributes for Analog Control Objects
Name
Meaning
Data Type
Engin.
Para.
OPC Prop.
OPC Item
ACKN
Acknowledge Command
Bool
CMD_ACKN
AUTOMAN
1
Auto/Manual Command
Bool
CMD_AUTOMA
N
RAISE
Raise Command
Bool
CMD_RAISE
LOWER
Lower Command
Bool
CMD_LOWER
HOLD
Hold Raise/Lower
Command
Bool
CMD_HOLD
SETVAL
1
Set Value (Y/W)
Command
Float
CMD_SETVAL
DMS
DMS command
Bool
CMD_DMS
AssocPV
Name of PV associated
with this object
String
x
RangeLow
Range low for setpoint
output
Float
28
x
RangeHigh
Range low for setpoint
output
Float
29
x
3.7.4.3 Specific Attributes for Control Objects Extended
3.7.4.3.1 General
Table 3-37: Specific Attributes for Control Objects Extended
25
CMD_OPEN for ASS
26
CMD_CLOSE for ASS
27
Depending on subtype, some commands are not applicable.
28
Derived from associated PV, =0 if PV not specified
29
Derived from associated PV, =100 if PV not specified