Product specifications
SPlus Operations P13 Connectivity Guide PROCONTROL P13 OPC SERVER
2VAA001153C 49
Table 3-17: Object IndividualXC80 Configuration
Field
Position
19
Meaning
XC80Ref
27
Generate:
Generate XC80
<AddrRef>
From bus with address reference
AddrRef
3.4.5.4 OPC Item Interface for XC80 Telegram
The information concerning the XC80-Telegram is provided via corresponding OPC items as shown in the table.
Table 3-18: OPC Items for XC80 Information
OPC Item
Meaning
Value
Quality
.XC80Tel
XC80 Telegram
GOOD
Defined and not disturbed bits show good
value
BAD
Telegram invalid due to invalid XC80 reference
NOT_CONNECTED
No XC80 configured
.XC80Def
Which bits are
defined
GOOD
Defined bit information valid
NOT_CONNECTED
No XC80 configured
.XC80Dist
Which bits are
disturbed
GOOD
Disturbed bit information valid
NOT_CONNECTED
No XC80 configured
.XC80Bus
Bus address
GOOD
XC80 Address configured
NOT_CONNECTED
XC80 Address not configured
.XC80Station
Station address
GOOD
XC80 Address configured
NOT_CONNECTED
XC80 Address not configured
.XC80Device
Device address
GOOD
XC80 Address configured
NOT_CONNECTED
XC80 Address not configured
3.5 OPC Alarm & Event
3.5.1 General
3.5.1.1 Event Categories
The event categories provided by PServer and the corresponding OPC Server:
Table 3-19: Event categories provided by PServer
Event Category
Description
OPC Event Type
Condition
Tracking
Simple
Process Message
Value events for PVs
x
Signal Message
Quality events for PVs
x
Limit
Limit events for analog PVs
x
Command Message [Simple]
Operator commands to process
x
[x]
System Message
PServer system messages
x
System Event
PServer system events (Alarms)
x
Event Suppression
Event suppression messages
x
3.5.1.2 Priorities and Severities
The mapping of PV priorities to OPC severities is done according to the following table:
19