Product specifications

SPlus Operations P13 Connectivity Guide PROCONTROL P13 OPC SERVER
32 2VAA001153C
3.3.3.3.1 Signals (AIX, AOX, DIX, AOX)
Table 3-8: PVE File Interface Signals Extended
Name
Meaning
Allowed Values
Default
Pos.
AIX
AOX
DIX DOX
Section
Process section

0
17
x
x
Inverted
Invert binary signal
Y, N, 1, 0
N
18
x
Unit
Measuring unit
Character string
-
18
x
DRLow
Display range low
Number
RLow
19
x
DRHigh
Display range low
Number
RHigh
20
x
NoDecs
Number of decimal digits

2
21
x
LimValue1
Value Limit 1
Number
DRLow/DRHig
h
22
x
LimValue2
Value Limit 2
23
x
LimValue3
Value Limit 3
24
x
LimValue4
Value Limit 4
25
x
LimType1
Type Limit 1
0: Upper
1: Lower
2: No limit
2
26
x
LimType2
Type Limit 2
27
x
LimType3
Type Limit 3
28
x
LimType4
Type Limit 4
29
x
LimTreat1
Treatment Limit 1
0: No message
1: Message for
Normal->Active
2: Message for
Active->Normal
3: Message both
directions
0
30
x
LimTreat2
Treatment Limit 2
31
x
LimTreat3
Treatment Limit 3
32
x
LimTreat4
Treatment Limit 4
33
x
LimPrio1
Priority Limit 1
0: State
message
1,2,3: Alarm
4: State
message
0
34
x
LimPrio2
Priority Limit 2
35
x
LimPrio3
Priority Limit 3
36
x
LimPrio4
Priority Limit 4
37
x
AlarmText1
Alarm Text Limit 1
Character string
>/<(LimValue1
)
38
x
NormText1
Normal Text Limit 1
Character string
</>(LimValue1
)
39
x
AlarmText2
Alarm Text Limit 2
40
x
AlarmText2
Alarm Text Limit 2
40
x
NormText2
Normal Text Limit 2
41
x
AlarmText3
Alarm Text Limit 3
42
x
NormText3
Normal Text Limit 3
43
x
AlarmText4
Alarm Text Limit 4
44
x
NormText4
Normal Text Limit 4
45
x