Product specifications

SPlus Operations P13 Connectivity Guide PROCONTROL P13 OPC SERVER
2VAA001153C 31
3.3.3.2 PVE File Interface
Table 3-7: PVE File Interface Standard PVs
Name
Meaning
Allowed Values
Default
Pos.
AIAO
DIDO
CO
Type
Type of the PV or parameter
set
AI, DI, AO, DO
ASS, ASM, ASE, GSA
VW2, VW3, VW4
# : Comment line Parameter set
VPCID
-
1
x
x
x
Name
Name of the PV
Character string
5
-
2
x
x
x
Descr
Description text
Character string
Name
3
x
x
x
Bus
Bus address

-
4
x
x
Station
6
Station address
0
7

-
5
x
x
Device
Device address

8
-
6
x
x
Bit
Bit address
0,...,F
-
7
x
RangeLow
Range low engineering unit
Number (float)
0
8
x
RangeHigh
Range high engineering unit
Number (float)
100
9
x
Text0
Text for Normal-state
Character string
0-State
8
x
Text1
Text for Active-state
Character string
1-State
9
x
Priority
Priority for events

4
10
x
EventDef
Event definition
0: No message
1: Message for Normal->Active
2: Message for Active->Normal
3: Message both directions
0
11
x
Alias
Alias name
Character string
-
12
x
x
Output
Output connection
4
Outputs without output
connection can be used e.g. as

{Y, N}
Y
13
x
9
x
3
x
10
AssocPV
Process Variable associated
with this one. Used to identify
the PV for the associated
setpoint value for analog
control objects.
Name of a Process variable
-
14
x
11
SpecProc
Special processing specifier:
For some object types a special
processing can be selected.
Character String, Example:
UBCD1:
Unsigned BCD from 1 word
For complete list of available
special processing see Table
3-22: Special Processing
Identifiers
15
x
12
NormPos
Normal Position:


event handling for digital
variables.
13
{0,1}
0
16
x
3.3.3.3 PVE File Interface - Extended PVs
In the following tables only the additional parameters are listed.
5
Naming convention must be observed to be able to use control objects and hierarchical browsing
6
Output variables (DO, AO) whose station address do not match the station address of the bus will be ignored
7
For output variables (DO, AO) station number 0 is interpreted as own station
8

9
For Outputs only
10

11
For analog control objects only
12
For AI only
13
The value itself will not be inverted