Product specifications

SPlus Operations P13 Connectivity Guide PROCONTROL P13 OPC SERVER
2VAA001153C 27
Table 3-3: Bus Configuration Parameters
Name
Meaning
Allowed Values
Coupler Type
Type of bus coupler.
{BK06, PIF, PCI PIF,
NotUsed}
Station Address
2
Number (Address) of the coupling station. For PIF
coupler, this address must match the station address
configured on the PIF board.

Port Number
Communication port (Serial or PIF) used for coupler.

PIF : 1,8
Poll Cycle
For BK06 only: Cycle in which BK06 should be polled.
Depending on the number of addresses to be polled,
the real poll cycle can be higher.

Code Switch
For BK06 only: Setting of the code switch on the BK06
front panel.
3

3.3.2.5 Command Channel Configuration
        -       
addresses for the standard command telegrams XC11, XC12 and XC13. For detailed explanation of this telegrams see
Figure 3-19.
Figure 3-19: Property Page for Command Channel Configuration
Remark:
Command telegrams whose address is set to 0 are assumed not to be used.
2
Output variables (DO, AO) whose station address do not match the station address of the bus will be ignored.
3
It has to be observed, that the BK06 code switch setting must 