Product specifications

SPlus Operations P13 Connectivity Guide PROCONTROL P13 OPC SERVER
2VAA001153C 23
3.3 Configuration and Engineering
3.3.1 Overview
The project-specific application data used by PServer can be classified as follows:
Site Configuration Parameters (.psc)
These parameters comprise the basic parameters concerning bus connections, VPC interfaces etc. They can
be modified through the PServer configuration user interface.
Process Variable Engineering Data (.pve)
These data comprise all parameters defining the process variables and control objects to be created for the
application.
Figure 3-11: Project-specific application data for PServer
3.3.2 Site Configuration Parameters
3.3.2.1 General
The Site Configuration Parameters determine the PServer-related site-specific properties of the Procontrol P13 control
system. The following parameters need to be configured,
VPC concept
Number and types of connected buses
Properties of used serial ports for BK06 connection
Properties of used I/O ports for PIF/PCI-PIF connection
Figure 3-12: Menu Tree for Site Parameter Configuration
Site configuration parameters are stored in a PServer site configuration file (.psc). On start-up, PServer loads the site
configuration file according to the recent file list, i.e. the file last accessed and existing is loaded.
PServer
P13 OPC
Configuration
File (.psc)
P13 OPC
Engineering
File (.pve)