Product specifications
SPlus Operations P13 Connectivity Guide PROCONTROL P13 OPC SERVER
2VAA001153C 19
Figure 3-3: Configure Procontrol OPC Server Service for Redundant Servers in a Domain
Remark:
Do enter the account in the form <Domain Name>\<User name> (e.g. INDUSTRIALIT\SPLUS), do not enter the
account in the form provided by Browse...!
To ensure, that the OPC Server will be started under the selected service account with the desired configuration
file (psc-file), login once with this account, start the OPC Server via Start Menu ->...-> PServer Configuration, open the
desired configuration file and exit again.
3.2.3 Start-up and Product Verification
By means of the OPC test clients included and the sample configuration provided, the installation can be verified by the
procedure as described here. After entering the site configuration and connecting the corresponding coupling hardware
(BK06, PIF) an appropriate test concerning this configuration must be performed. This test procedure assumes that the
data access client and the event client have been installed.
1. Start Data Access Client and connect it to the ABB Procontrol OPC Server
Select: Start-> Program Files -> ABB P13 Connect OPC Server ->Data Access Client. In the data access client
select: OPC->Connect. This will bring up the Select OPC Server dialog. In the list of available servers, the ABB
Procontrol Server must appear. Select this and leave with OK.