Product specifications

SPlus Operations P13 Connectivity Guide PROCONTROL P13 OPC SERVER
18 2VAA001153C
Parity
Configurable
Flow control
None
Baud rate
Configurable
For details of BK06 programming see BK06Programming.
3.2.1.2 PIF
The settings on the PIF hardware listed in the following table must match the corresponding PIF configuration
parameters in PServer.
Table 3-2: PIF Settings
Parameter
Value
I/O channel
(Address range)
Select a free channel
Station Address
According to plant configuration
Interrupt level
Select a free level
(Or disable interrupt in PServer)
For details of PIF hardware configuration see PIF Users Guide 1KHZ 102 655.
3.2.2 OPC Server Service Configuration
A good practice for the OPC Server service configuration is, to use the same account for the OPC Server as used for
the S+ Operations, e.g. SPLUS. In order to create the Service, execute the OPC Server via Start Menu ->ABB P13
Connect OPC Server-> PServer Create Service
Figure 3-2: Configure Procontrol OPC Server Service for Redundant Servers in a Workgroup