Datasheet

66 Miniature Circuit Breakers | US Catalog
Combined auxiliary and bell alarm
Usage category AC15 400/2 A-UL
AC15 240/6A-UL
DC13 250/0.55 A125 V/1.1A-IEC
DC13 125 V/1.1A-IEC
DC13 60 V/2A
DC13 24 V/4A
Continuous thermal current I
n
6 A
Rated insulation voltage U
i
690 V
Number of contacts 2 (1x AUX, 1 x AUX/ALT)
Surge U
test
(1.2/50μs) 6 kV
Degree of protection 3
Function of contact Changeover contacts
Connection CU 1 x 2.5 mm
2
2 x 1.5 mm
2
Tightening torque 1 Nm
Ensured contacts during shake test 5g, 20 frequency cycle
acc. to IEC 68-2-6 5...150...5 Hz at 24 VAC/DC, 5 mA brief interrupt <10 ms
AC/DC supply any EN 60715
Mounting on DIN top hat rail EN 60715
Type of protection IP20
Permissible ambient temperature for operations -25...+60
º
C; -13
º
F...140
º
F
Storage temperature -40...+70
º
C; -40
º
F...150
º
F
Mechanical device service life 6000 switching cycles
I
cu
with S450E 1000 A
Resistance to vibration IEC 60068-2-27;
IEC 60068-2;
EN 61373 Cat. 1/class B
Shunt operation release — S800-SOR
S800-SOR24 S800-SOR130 S800-SOR250 S800-SOR400
Rated voltage U
e
24 VAC/DC 48...130 VAC/DC 110...250 VAC/DC 220...250 VAC/DC
Operating range 70...110% Ue
Rated insulation voltage U
i
690 V
Coil pull in consumption 19.2 W/vA On request
Rated frequency DC; 50/60 Hz
Protection degree 3
Connection Cu 1...35 AWG
Tightening torque min. 3/max. 4 Nm
AC/DC supply Any
DIN top hat rail EN 60715
Type of protection IP20
IP40 (only actuation side)
Permissible ambient temperature of operations -25...+60
°
C; -13
°
F...140
°
F
Storage temperature -40...+70
°
C; -40
°
F...158
°
F
S800-UVR36 IEC 60068-2-27; IEC 60068-2; EN61373 Cat. 1/class B
Technical specifications
S800U-UL