Datasheet

US Catalog | Miniature Circuit Breakers 63
Technical specifications
S800
Characteristics
S800U
K, Z
Rated operational current I
e
[A] 10...100
Pole 1...4
Rated operational voltage U
e
compliant to UL489
(AC) 50/60 Hz [V] 240
Rated ultimate short-circuit breaking capacity compliant to UL489
(AC) 50/60 Hz 240 V Single-pole [kA] 30
(AC) 50/60 Hz 240 V Multi-pole [kA] 50
Rated operational voltage U
e
compliant to IEC 60947-2
(AC) [V] 240/415
Rated ultimate short-circuit breaking capacity I
cu
compliant to IEC 60947-2
(AC) 50/60 Hz 240/415 V Single-pole [kA] 30
(AC) 50/60 Hz 240/415 V Multi-pole [kA] 50
Rated service short-circuit breaking capacity I
cs
compliant to IEC 60947-2
(AC) 50/60 Hz 240/415 V Single-pole [kA] 25
(AC) 50/60 Hz 240/415 V Multi-pole [kA] 40
Connections C
u
10...30 A 14-2 AWG
40...100 A 8-1 AWG
Rated frequency 50/60
Tightening torque [Hz] 3,5 (31 in. lb.)
Protection category [Nm] IP40
(actuating end only)
Mounting position Any
Contacts Cadmium-free
Permissible ambient temperature [
ยบ
C] -25...+60
Standards UL489
IEC 60947-2
CSA22.2 No.5-02
Approval cULus
File E312425