Datasheet
US Catalog | Miniature Circuit Breakers 61
Description (for field mounting, left side) Catalog number
Shunt operation release 24 VAC/DC S800-SOR24
Shunt operation release 48...130 VAC/DC S800-SOR130
Shunt operation release 110...250 VAC/DC S800-SOR250
Description Catalog number
Undervoltage release 24...36 VAC/DC S800-UVR36
Undervoltage release 48...60 VAC/DC S800-UVR60
Undervoltage release 110...130 VAC/DC S800-UVR130
Undervoltage release 220...250 VAC/DC S800-UVR250
Description Catalog number
Auxiliary contact S800-AUX
Description Catalog number
Bell alarm S800-AUX/ALT
Description Catalog number
Ring terminal cable connection, 40-125 A S800-RT2125
Accessories
S800U
S800-UVR
S800-AUX
S800-AUX/ALT
S800-SOR
S800-RT2125
Shunt trip
For remote tripping of breaker, a shunt trip device can be added to the MCB. The device opens
the breaker after control voltage is applied.
Undervoltage release
When control voltage drops below approximately 50 percent of rated voltage, the UVR opens the
breaker. The breaker cannot be operated unless proper control voltage is first applied to the UVR coil.
Auxiliary contacts
The auxiliary contacts will signal whether the breaker is in the ON or OFF position.
Bell alarm
The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically,
the contacts would be connected to an alarm or bell to signal the operator that an overcurrent
trip has occurred. The bell alarm also includes a test button for testing the alarm contacts without
opening the breaker.