Datasheet
US Catalog | Miniature Circuit Breakers 57
jumper jumper jumper jumper
jumper jumper
jumper
jumperjumperjumperjumper
jumper
jumper jumper
Line and load migth be reversed
jumper
+
LOAD
LOAD
+
-
LOAD
+
-
+
-
LOAD
LOAD
LOAD
+
+
-
+
-
Ampere rating (A)10–32
Conductor type
Single conductor per terminal –
copper only, 60/75
º
C wire
AWG, wire range
Jumper length (cm)
Jumper length (ft)
14 AWG–2 AWG
Cu, solid or stranded
1
30.5
40–63
Single conductor per terminal –
copper only, 60
º
C wire only
1/0 AWG–8 AWG
Cu, solid or stranded
1
30.5
70–80
Single conductor per terminal –
copper only, 60
º
C wire only
1/0 AWG–8 AWG
Cu, solid or stranded
2
61
jumper jumper jumper jumper
jumper jumper
jumper
jumperjumperjumperjumper
jumper
jumper jumper
Line and load migth be reversed
jumper
+
LOAD
LOAD
+
-
LOAD
+
-
+
-
LOAD
LOAD
LOAD
+
+
-
+
-
Ampere rating (A)10–32
Conductor type
Single conductor per terminal –
copper only, 60/75
º
C wire
AWG, wire range
Jumper length (cm)
Jumper length (ft)
14 AWG–2 AWG
Cu, solid or stranded
1
30.5
40–63
Single conductor per terminal –
copper only, 60
º
C wire only
1/0 AWG–8 AWG
Cu, solid or stranded
1
30.5
70–80
Single conductor per terminal –
copper only, 60
º
C wire only
1/0 AWG–8 AWG
Cu, solid or stranded
2
61
Tripping behavior acc. to UL489
Thermal tripping: 1.00…1.35 x I
e
Electromagnetic tripping 11 x I
e
± 20 %
95
142
45
35
79.5
53
26.5
1P 2P 3P 4P
106
2CCC413012Z0001
76.5
46
82.56
Dimension of S804U-UCZTrip curves for S804U-UCZ
S804U-UCZ
Tested and listed wirings
Line and load might be reversed