Datasheet

18 Miniature Circuit Breakers | US Catalog
Electrical data Busbars PS…BP-C/CR
Standards UL508
EN 60947-1 / IEC 60947-1:2004
Rated voltage U
e
V 600 V AC/DC
Rated frequency Hz 50 Hz (IEC) / 60 Hz (UL)
Rated impuls withstand voltage Uimp. kV ≥ 10 kV
Rated current / phase
End fed
1)
A 100 A
Center fed
1)
A 200 A
Short circuit current rating kA 10 kA 3 cycles @ 600 V / 140 kA Fuse Class J 200 A
Mechanical data
Housing grey, RAL 7035
Resistance to climatic conditions acc. to DIN EN 60068
Isolation coordination
Overvoltage category III
Pollution degree 2
Installation
Cross section mm² 25 mm²
Mounting position Optional
Supply Via cable with ring lug (PS...BP-CR); direct or via feeder terminal (PS...BP-C)
Accessories
Shock protection caps BSK BP-CR (for PS...BP-CR), BSK BP-C (for PS...BP-C)
Endcaps PS-END 3 BP-C
Approvals
CE, RoHS
UL 508: cULus Listed
1)
Independently from the current rating of the feeder terminal or busbar, the current-carrying capacity/current rating of the MCB terminal must not be exceeded.
10.50
1.8
22
Technical specifications
Busbars PS...BP-C/CR and accessories
Installation/assembly
Warning: When busbars are shortened, they must be deburred and cleaned of debris. Touch-safe only when used with the required
end caps.
Dimensional drawing
17.60
950-1003
5.00
19.3
1.8