Datasheet
16 Miniature Circuit Breakers | US Catalog
SU200MR
Rated current Internal resistance per pole
1)
Power loss per pole
1)
A mΩ W
0.2 25300 1.01
0.3 13700 1.23
0.5 4740 1.19
0.75 2067 1.16
1 1270 1.27
1.5 610 1.56
2 442 1.77
3 140 1.26
4 109 1.75
5 50 1.26
6 54 1.94
8 22 1.41
10 18.2 1.82
13 14.8 2.50
15 8.1 1.83
16 11.1 2.83
20 8.5 3.40
25 5.5 3.43
30 3.8 3.39
32 4.6 4.70
35 3.9 4.76
40 2.8 4.40
50 1.7 4.25
60 1.7 6.18
63 1.9 7.56
1)
Internal resistances and power loss are subject to application-specific and environment-specific conditions and are therefore to be considered as typical values.
SU200M
C, K characteristics Z characteristics
Rated current Internal resistance per pole Power loss Internal resistance per pole Power loss
I
n
R
i
P
v
R
i
P
v
A mΩ W mΩ W
0.2 42500 1.7 - -
0.3 18889 1.7 - -
0.5 5600 1.4 9000 2.3
0.75 2489 1.4 - -
1 1400 1.4 2200 2.2
1.6 703 1.8 1000 2.6
2 450 1.8 650 2.6
3 178 1.6 250 2.3
4 113 1.8 140 2.2
5 50 1.3 100 2.5
6 56 2.0 70 2.5
8 23 1.5 28 1.8
10 21 2.1 21 2.1
13 14 2.3 17 2.9
15 11 2.4 13 2.9
16 9.8 2.5 10 2.6
20 6.3 2.5 6.5 2.6
25 5.1 3.2 5.1 3.2
30 3.9 3.5 3.9 3.5
32 3.6 3.7 3.6 3.7
35 3.3 4.1 3.3 4.1
40 2.8 4.5 2.8 4.5
50 1.8 4.5 1.8 4.5
60 1.4 4.9 1.4 4.9
63 1.4 5.4 1.4 5.4
Internal resistances are subject to application-specific and environment-specific conditions and are therefore to be considered as typical values.
Technical specifications
SU200M, SU200MR, and S200UDC—UL 489, CSA 22.2 No. 5
Internal resistance and power loss per pole
Internal resistance per pole in mV, power loss per pole in W.