Fault and Alarm Status
The ACS 160 provides fault and alarm status words for the external control
system. These data words are accessible only through the serial
communication link but not from the control panel.
Fault and alarm status words are located in parameter group 3. The group also
contains copies of the Control Word and Status Word. Group 3 parameters are
of read-only type; however, both alarm words can be reset by writing a zero to
them.
Table 4-8 Fault and alarm status words.
No Name Description
40301
MAIN COMMAND
WORD
Read-only copy of the Command Word
(40001). See page 4-4.
40302
MAIN STATUS
WORD
Read-only copy of the Status Word (40004).
See Table 4-6.
40305
FAULT WORD 1
Fault information. When a fault is active
corresponding bit is set. Bit descriptions are
given in Table 4-9.
40306
FAULT WORD 2
Fault information. When a fault is active, the
corresponding bit is set. Bit descriptions are
given in Table 4-9.
40308
ALARM WORD 1
Alarm information. When an alarm is active
corresponding bit is set. Bits remain set until
whole alarm word is reset by writing 0 to it.
See Table 4-10.
40309
ALARM WORD 2
Alarm information. When an alarm is active
corresponding bit is set. Bits remain set until
whole alarm word is reset by writing 0 to it.
See Table 4-10.