Technical data
Chapter 4 – Communication
RS485 and RS232 Adapter Installation and Start-up Guide 4-11
Actual Values
Actual values are read-only values containing information on the operation of
the drive. Actual values are 16-bit words containing sign bit and a 15-bit
integer. A negative value is given as two’s complement of the corresponding
positive value.
Actual Value 1
Holding Register: 40005
Actual output frequency. Scaling: 5000 50 Hz.
Actual Value 2
Holding Register: 40006
Actual output current. Scaling: 10 1 A.