Technical data

Chapter 4 Communication
RS485 and RS232 Adapter Installation and Start-up Guide 4-7
Table 4-6 The Status Word
Bit Value Description
01
ready to switch on
0
not ready to switch on
11
ready to operate
0
off1 active
21
operation enabled
0
Not ready (OPERATION INHIBITED)
30 - 1
fault
0
No fault
41
OFF2 inactive
0
OFF2 ACTIVE
51
OFF3 inactive
0
OFF3 ACTIVE
61
switch-on inhibited
0
71
Alarm is active. See Diagnostics section for a list of relevant
alarms.
0
No alarm
81
OPERATING. Actual value equals reference value (= is within
tolerance limits).
0
Actual value differs from reference value (= is outside tolerance
limits)
91
Drive control location: REMOTE
0
Drive control location: LOCAL
10 1
The value of first supervised parameter equals to or is greater than
supervision limit. Refer to Group 32 Supervision.
0
The value of first supervised parameter is below supervision limit
11 1
External control location 2 (EXT2) selected
0
External control location 1 (EXT1) selected
12 1
Run Enable signal received
0
No Run Enable signal received
13 to
15
Unused