Technical data

Chapter 3 Programming
3-6 RS485 and RS232 Adapter Installation and Start-up Guide
Diagnostic Counters
Diagnostic counters can be used for debugging the Modbus system.
Counters will roll over from 65535 to 0. The counter values are stored to
permanent memory when power is disconnected.
Counters can be reset from the control panel by pressing the UP and DOWN
buttons simultaneously when in parameter set mode, or by setting them to zero
via the serial communication channel.
Note! Parameters 5206 - 5212 are displayed in hexadecimal format by the
control panel. The panel displays three decimal points to indicate a
hexadecimal number control panel.
Figure 3-1 An example of the control panel displaying a hexadecimal number
A14 (2580 decimal).
Code Name Range User
Group 52
SERIAL COMM
5206 BAD MESSAGES 0 - 65535
5207 GOOD MESSAGES 0 - 65535
5208 BUFFER OVERRUNS 0 - 65535
5209 FRAME ERROS 0 - 65535
5210 PARITY ERROS 0 - 65535
5211 CRC ERROS 0 - 65535
5212 BUSY ERROS 0 - 65535
5213 SER FAULT MEM 1 0 - 3
5214 SER FAULT MEM 2 0 - 3
5215 SER FAULT MEM 3 0 - 3