Technical data

Chapter 2 Installation
RS485 and RS232 Adapter Installation and Start-up Guide 2-5
Selecting RS485 or RS232 Mode
The adapter operates either in RS232 mode or in RS485 mode, selectable by a
jumper. As a factory setting, the adapter operates in RS485 mode.
Figure 2-4 Selecting the operating mode.
RS485 Bus Termination
The RS485 bus must be terminated using 120 9 resistors at both ends of the
network. The adapter has built-in termination resistors that can be enabled by
the bus termination switch S1. Refer to 'Earthing and Termination' on page 2-
11. By default, bus termination is enabled (ON).
Figure 2-5 Selecting RS485 termination impedance.
Jumper S3
Mode
RS485
RS232
1
2
S3
Bus termination switch
S1