Technical data
1
07 KP 95 / Issued: 09.97
07 KP 95
1 Communication processor 07 KP 95 R101
Communication over the Advant Fieldbus 100
Fig. 1: Communication processor 07 KP 95 R101
F R
07KP95
CI520
Contents
1.1 Brief description 1. . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Features of the unit 07 KP 95 1. . . . . . . . . . . . . .
1.3 Survey of Advant Fieldbus (AF100),
07 KP 95 and ABB Procontic CS31 2. . . . . . . . .
1.4 Structure of the front panel 2. . . . . . . . . . . . . . . .
1.5 Electrical connection 2. . . . . . . . . . . . . . . . . . . . .
1.5.1 Application examples for AF100
coupling with modem, coupler 07 KP 95
and central unit 2. . . . . . . . . . . . . . . . . . . . . . . . . .
1.5.2 Connection of the supply voltage 5. . . . . . . . . . .
1.5.3 Networking interface 5. . . . . . . . . . . . . . . . . . . . . .
1.5.4 Measures for RFI 5. . . . . . . . . . . . . . . . . . . . . . . .
1.7 Technical data 6. . . . . . . . . . . . . . . . . . . . . . . . . . .
1.8 Ordering data 8. . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Brief description
The communication processor 07 KP 95 allows interfac-
ing of ABB Procontic CS31 to the AF100 (Advant Field-
bus 100). The communication processor 07 KP 95 needs
additionally a communication interface CI520 and an ap-
propriate bus modem. The 07 KP 95 contains the carrier
board for the CI520 (similar to the Submodule Carrier
Board with the Advant Controller 450, but the 07 KP 95
has only one slot for one CI520).
The programming of the communication processor is car-
ried out in the PLC program with a PC using the program-
ming and test system 907 PC 331.
The programming software 907 KP 95 provides all con-
nection elements necessary for operating the commu-
nication processor 07 KP 95:
● AF100
● DSPIN
● DSPOUT
● DWREAL
● REALDW
1.2 Features of the unit 07 KP 95
The following functions are supported by the 07 KP 95:
– master or slave at the AF100 (function block AF100)
– single-channel or redundant configuration of the
AF100 (selectable via the function block AF100)
– transmission of cyclic data using the function blocks
DSPIN and DSPOUT (max. 475 DSPs with 8 DATs,
max. 250 DSPIN and 249 DSPOUT)
– service data: station, type, version, status
– no event handling
– no time-sync
– no program-load