Technical data
7
907 KP 95 / Issued: 09.97
CEs
READ DSP FROM THE AF100 COUPLER 07 KP 95 DSPIN
#CT DIRECT CONSTANT
At the input #CT the transmission interval (cycle time) is
defined in ms. This input defines, how many times a DSP
is transmitted on the bus.
Valid values: 1, 2, 4, 8, 16, 32, 64, 128, 256, 512,
1024, 2048, 4096
VAL BINARY
At the output VAL it is indicated, that the data of the confi-
gured flag ranges are valid. The output VAL is reset to
zero, if within (3 * #CT) no valid data has been received.
ERR BINARY
At the ERR output it is indicated, whether an error has oc-
curred.
In case of an error (partner is no 07 KP 95 or the AF100
coupler 07 KP 95 disables the dual–port RAM), the output
ERR is set to 1.
The inputs and outputs can neither be doubled nor in-
verted.
____________________________________________________________________________________________
CE data
Runtime: 07 KR 91/07 KT 92/07 KT 93
Basic runtime: µs
Additional runtime:
Updating of the outputs: yes
Number of historical values: 0 words
Available as of: ABB Procontic CS31 07 KR 91 R202/R252 index c
07 KT 92 R202/R262 index c
07 KT 93 R101 index f