Technical data
4
907 KP 95 / Issued: 09.97
CEs
AF100 INITIALIZATION OF THE AF100 COUPLER 07 KP 95
#STN DIRECT CONSTANT
At the input #STN, the own station number is given.
Valid values: 1 <
#STN < 80
#MAS DIRECT CONSTANT
At the input #MAS it is given whether the coupler is a bus
master or a bus slave.
Values: #0: bus slave, #1: bus master
#TSY DIRECT CONSTANT
The input #TSY is a reserved input.
Valid value: #0
#CAB DIRECT CONSTANT
At the input #CAB it is defined, whether the AF100 bus is
configured redundant or not.
Values: #0: singe–channel, #1: redundant
#SCT DIRECT CONSTANT
The input #SCT is a reserved input.
Valid value: #0
WARN BINARY
At the output WARN it is indicated, whether a warning has
appeared during operation (see DIAG).
ERR BINARY
At the output ERR it is indicated, whether an error has ap-
peared during operation (see DIAG).
DIAG DOUBLE WORD
At the output DIAG, the diagnosis information is indi-
cated. The output is coded binary. It is possible that sev-
eral bits are set to 1 in the diagnosis double word (DIAG =
65, i.e. ACT = 1 and CRA = 1 (bit 0 and bit 6)).
Meaning of the bits in the double word:
DIAG = 1: the coupler is active (ACT);
if the coupler is not active, WARN is
set to 1 (bit 0 of DIAG = 1).
DIAG = 2: severe error (SE);
a SE causes ERR = 1
(bit 1 of DIAG = 1).
DIAG = 4: hardware error (HWE);
a HWE causes WARN = 1
(bit 2 of DIAG = 1).
DIAG = 8: software error (SWE);
an SWE causes ERR = 1
(bit 3 of DIAG = 1).
DIAG = 16: peripheral hardware error (PHE);
a PHE causes WARN = 1
(bit 4 of DIAG = 1).
DIAG = 32: process errors (PRE);
a PRE causes WARN = 1
(bit 5 of DIAG = 1).
DIAG = 64: cable redundancy available (CRA)
(bit 6 of DIAG = 1).
DIAG = 128: redundant cable 1 failed (RC1);
an RC1 causes WARN = 1
(bit 7 of DIAG = 1).
DIAG = 256: redundant cable 2 failed (RC2);
an RC2 causes WARN = 1
(bit 8 of DIAG = 1).
DIAG = 512: redundant power A failure (RPA);
an RPA causes WARN = 1
(bit 9 of DIAG = 1).
DIAG = 1024: redundant power B failure (RPB);
an RPB causes WARN = 1
(bit 10 of DIAG = 1).
DIAG = 16384: general error (GE);
a GE causes ERR = 1
(bit 14 of DIAG = 1).
DIAG = -32768: general warning (GW);
a GW causes WARN = 1
(bit 15 of DIAG = 1).
ERR1 BINARY
The output ERR1 indicates, that the redundant cable 1 is
defective (WARN = 1 and ERR1 = 1).
ERR2 BINARY
The output ERR2 indicates, that the redundant cable 2 is
defective (WARN = 1 and ERR2 = 1).
The inputs and outputs can neither be doubled nor in-
verted.
____________________________________________________________________________________________
CE data
Runtime: 07 KR 91/07 KT 92/07 KT 93
Basic runtime: µs
Additional runtime:
Updating of the outputs: yes
Number of historical values: 1 word
Available as of: ABB Procontic CS31 07 KR 91 R202/R252 index c
07 KT 92 R202/R262 index c
07 KT 93 R101 index f
07 KT 93 R171 index f