Technical data

3
907 KP 95 / Issued: 09.97
CEs
INITIALIZATION OF THE AF100 COUPLER 07 KP 95 AF100
FBD/LD
IL
AF100
0/1
#BUS
#STN
ERR1
WARN
ERR
DIAG
!BA
AF100
0
M 00,00
#1
#1
#1
#0
M 00,00
#1
#1
#1
A 00,01
MD 00,00
A 00,02
A 00,03
#MAS
#TSY
#CAB
#SCT
ERR2
AF100
0/1
#BUS
#STN
ERR1
WARN
ERR
DIAG
#MAS
#TSY
#CAB
#SCT
A 00,00
#0
#0
#0
#0
A 00,00
A 00,01
MD 00,00
ERR2
A 00,02
A 00,03
#0
Parameters
0/1 BINARY E, M, A, K, S Enable block processing
#BUS DIRECT #, #H Bus number; valid values: 1...255
CONSTANT insignificant for CS31
#STN DIRECT #, #H Own station number; valid values: 1...80
CONSTANT
#MAS DIRECT #, #H AF100 bus master/slave:
CONSTANT #0: bus slave, #1: bus master
#TSY DIRECT #, #H Reserved; valid value: #0
CONSTANT
#CAB DIRECT #, #H #0: no redundant AF100 bus (1 cable)
CONSTANT #1: redundant AF100 bus (2 cables)
#SCT DIRECT #, #H Reserved; valid value: #0
CONSTANT
WARN BINARY A, M Warning (not a fatal error)
ERR BINARY A, M An error has occurred (hardware or configuration)
DIAG DOUBLE WORD MD Diagnosis
ERR1 BINARY A, M WARN = 1 and ERR1 = 1: redundant cable 1 failed
ERR2 BINARY A, M WARN = 1 and ERR2 = 1: redundant cable 2 failed
____________________________________________________________________________________________
Description
The function block initializes the AF100 coupler
07 KP 95.
Important note:
During program modifications on running programs the
AF100 function block must not be deleted, and the inputs
of the AF100 function block must not be altered.
0/1 BINARY
After an 0/1 edge at the input 0/1 the AF100 coupler is ini-
tialized to the relevant values. After initialization, further
0/1 edges are ignored.
#BUS DIRECT CONSTANT
At the input BUS, the number of the AF100 bus is defined.
This input has no meaning in connection with CS31. The
coupler can contain only 1 CI520.
Valid values: 1 <
BUS < 255