Technical data
5
07 KP 95 / Issued: 09.97
07 KP 95
1.5.2 Connection of the supply voltage
24 V DC
As shown in Fig. 3 and Fig. 4, the supply voltage for the 07
KP 95 is looped through from the CS31 central unit (red
wire = L+, blue wire = M).
1.5.3 Networking interface
The networking interface, a special parallel interface, al-
lows the 07 KP 95 communication processor to be con-
nected to ABB Procontic CS31 central units 07 KT 93.
The housing of the communication processor is con-
nected to the housing of the ABB Procontic central unit by
a snap–fit connection. The electrical connection is via a
40–pole ribbon cable with socket connector, soldered
onto the 07 KP 95 R101 side.
Note: Attachment and disconnection of units on the net-
working interface may only be performed when all supply
voltages are switched off.
Mounting the communication processor at the net-
working interface
1. Detach the cover on the central unit (e.g. 07 KT 93)
from the networking interface.
2. Plug the socket strip of the 40–pole ribbon cable se-
cured to the 07 KP 95 R101 onto the networking con-
nector of the CS31 central unit.
3. Slide both units together.
4. Slide the replacement cover provided with the
07 KP 95 unit with its cut-out onto the networking in-
terface.
1.5.4 Measures for RFI (Radio Frequency Inter-
ference)
– Installation in a metallic switch–gear cabinet
– Mains filters