Installation manual

183
Siemens
Siemens
65 Siemens
65�1 Siemens
Easy Installation Termination Addressing Sensors RS485 Meters RS485 Interface
Yes Resistor Yes
Yes Yes RS485
Overview
•
Integrated interface
•
Where to connect: RJ45 socket on the bottom of the inverter
•
2-pin wiring
•
Communication address must be allocated.
•
Installation steps
Switch off the inverters and Solar-Log™
Connect inverters to the Solar-Log™
Connect the inverters to each other
Allocate communication address
Connect inverters to the Solar-Log™
To connect the Solar-Log™ and the inverters prepare cables with the following pin allocation.
Connecting the Solar-Log™ to the first inverter
Solar-Log™ (4/6 pin terminal plug) First inverter - RS485 IN
(4-pin round plug)
Pin 1 (white) Pin 2
Pin 4 (brown) Pin 3
If only one inverter is to be connected this must be terminated (see following item "Bus termination").
Connect the inverters to each other
Inverters must be connected to each other using shielded data cables via the RS485 connections
located on the SINVERT PVM.
The following illustration shows the main connection diagram.
Figure 12: Siemens – connecting inverters together