Installation manual

119
KLNE
KLNE (Solartec and Sunteams)
Solar-Log™ terminal strip connector X4 socket inverter
Terminal PIN
1
4 - Data+
4
2 - Data-
3. Connect the Solar-Log™ cable to socket A on the first inverter.
4. According to the same wiring diagram, connect socket B on the first inverter to socket A on the
second inverter using the following diagram.
X4 socket inverter 1 X4 socket inverter 2
Terminal PIN
2
2 - Data+
4
4 - Data-
5. Connect the other inverters to each other in the same way.
6. 6 Terminate the last inverter in accordance with the inverter instructions.
7. Insert the terminal block connector into the Solar-Log™ RS485 socket.
Note:
According to the manufacturer's specifications, a maximum of 31 devices can be connected
per RS485 bus.