Cut Sheet
Operation -25 ... +60 °C
Operation Compensated -25 ... +60 °C
Storage -50 ... +80 °C
Ambient Air Temperature
Yes Ambient Air Temperature Compensation
2000 m Maximum Operating Altitude Permissible
11 ms Pulse 25g Resistance to Shock acc. to IEC 60068-2-27
5g / 3 ... 150 Hz Resistance to Vibrations acc. to IEC 60068-2-6
Following EU Directive 2011/65/EU RoHS Status
Environmental
—
Main Circuit 600 V AC Maximum Operating Voltage UL/CSA
54 A Ampere Rating UL/CSA
(200 V AC) Three Phase 15 Hp
(208 V AC) Three Phase 15 Hp
(220 ... 240 V AC) Three Phase 20 Hp
(440 ... 480 V AC) Three Phase 40 Hp
(550 ... 600 V AC) Three Phase 50 Hp
Horsepower Rating UL/CSA
(200 V AC) Three Phase 48.3 A
(208 V AC) Three Phase 46.2 A
(220 ... 240 V AC) Three Phase 54 A
(440 ... 480 V AC) Three Phase 52 A
(550 ... 600 V AC) Three Phase 52 A
Full Load Amps Motor Use
(200 V AC) Three Phase 267 A
(208 V AC) Three Phase 257 A
(220 ... 240 V AC) Three Phase 290 A
(440 ... 480 V AC) Three Phase 290 A
(550 ... 600 V AC) Three Phase 290 A
Locked Rotor Amps
(600 V AC) 54 A General Use Rating UL/CSA
Flexible 1/2x 16-0 AWG
Stranded 1/2x 16-0 AWG
Connecting Capacity Main Circuit UL/CSA
Main Circuit 35 in·lb Tightening Torque UL/CSA
Technical UL/CSA
—
1SAA963002-0101 ABS Certificate
1SAA918001-3901 ATEX Certificate
1SAA963002-0201 BV Certificate
1SAA918002-2002 CB Certificate
1SAA918004-3801 CCC Certificate
cUL_E345003 cUL Certificate
1SAD938501-0198 Declaration of Conformity - CE
1SAA963002-0301 DNV GL Certificate
1SAA963002-2701 EAC Certificate
2CDC131081M6801 Instructions and Manuals
1SAA963001-1501 KC Certificate
1SAA918001-0501 LR Certificate
1SAA918000-0704 RMRS Certificate
1SAD938501-0198 RoHS Information
cUL_E137861
UL_E137861
cUL_E345003
UL Certificate
Certificates and Declarations (Document Number)
—
3 MS165-54